3x4-8
2025/05/23 10:37
---Duty Point---
Flow: 100 m³/hr
Head: 55.5 m
Eff: 74%
Power: 15.4 kW
NPSHr: 3.05 m
--- Design Curve ---
Shutoff Head: 60 m
Shutoff dP: 444 kPa
Min Flow: 31.5 m³/hr
BEP: 82.7% @ 157 m³/hr
NOL Power:
21.6 kW @ 213 m³/hr
--- Max Curve ---
Max Power:
25.5 kW @ 226 m³/hr